Fire collars and wraps
Plastic pipes melt in a fire. A collar or wrap swells up and closes the hole they leave.
- Every seal labelled and photographed
- BM TRADA / FIRAS-certificated contractors
- Written price before any work
Plastic pipe goes soft and collapses in a fire. Then there is an open hole in the floor the size of the pipe.
An intumescent collar or wrap stops that. The material inside swells when it heats up, crushes the soft pipe and fills the hole.
Collar or wrap
A collar is a steel ring with intumescent inside. It is screwed to the face of the wall or the underside of the floor, round the pipe.
A wrap is a strip of intumescent wound round the pipe and pushed into the hole, flush with the face of the wall or floor. No visible ring.
Which one is used depends on the maker's tests. Some wraps are tested in concrete floors and not in plasterboard walls. Some collars need to go on both faces of a wall, some on one face only.
Sizing
Collars and wraps come in pipe sizes. A 110mm soil stack needs a 110mm collar, not a 160mm one taped on. Pipe lagging, if there is any, changes the size again.
A made-up riser in a block of flats, floor 4:
110mm soil stack through the slab. Old collar fitted on top of the slab instead of underneath. Moved underneath.
40mm waste added later, no collar. Wrap fitted.
22mm copper heating pipes. Not plastic, so no collar. Mastic.
15mm plastic water pipe in a plastic sleeve. Wrap sized to the sleeve.
Where they get missed
New bathrooms. A plumber adds a waste and runs it through the floor or the riser wall.
Kitchen refits in flats, when the waste is rerouted.
Condensate pipes from new boilers. Small, plastic and often through a fire wall.
Fitting and record
Our BM TRADA / FIRAS-certificated contractors fit the collars and wraps. Each one gets a tag with its number, and the record lists pipe size, product and rating.
Tell us the postcode, what the building is used for and how many floors it has. Photos of the gaps help a lot.